What does the Florida Building Code require for underlayment?
The code lists the approved standards and three ways to install shingle underlayment. Every approved material must carry a label showing its standard and type.
Section R905.1.1 of the Florida Building Code, Residential (2023) says underlayment must meet one of these standards: ASTM D226, D1970, D4869, D6757 or D8257. The label has to show the standard and any type. For asphalt shingles, Section R905.1.1.1 gives three methods:
- Full self-adhering membrane. A self-adhering polymer-modified bitumen sheet, ASTM D1970, covers the whole deck.
- Tape on the seams. A strip at least 3 3/4 inches wide of ASTM D1970 membrane or AAMA 711 Level 3 flashing tape goes over every joint in the deck. An approved underlayment then covers the whole roof.
- Two layers. Two layers of ASTM D226 Type II, ASTM D4869 Type III or IV, or ASTM D8257. The first course is a half-width strip at the eaves, and the second is a full sheet from the eave.
The code also sets the laps and nails for the two-layer method: 6-inch end laps offset 6 feet, fasteners at most 12 inches apart between side laps and 6 inches apart at the end and side laps, and caps at least 1 inch across. Metal caps are required where the ultimate design speed is 170 mph or more.
On a roof replacement, the existing building code adds a secondary water barrier requirement. When a covering is removed and replaced on a wood deck, Section 706.7.2 says a secondary water barrier must be installed to Section R905.1.1 of the residential code or the building code's equivalent. Roofs below 2:12 with a continuous system, and clay or concrete tile installed to code, are exempt. For the wider chapter, see our guide to the Florida Building Code for roofing.